1. Fampidirana
This manual provides comprehensive instructions for the installation, operation, and maintenance of the Acrel DTSD1352 Three Phase Bidirectional Energy Meter. This device is designed for accurate measurement of three-phase energy consumption and generation, featuring RS485 communication for integration into monitoring systems. Please read this manual thoroughly before installation and operation to ensure safe and efficient use.
2. Information momba ny fiarovana
FAMPITANDREMANA: Atahorana hihozongozona elektrika!
- Ny fametrahana sy fikojakojana dia tsy tokony hatao afa-tsy amin'ny elektrisianina mahay.
- Ensure all power is disconnected before installing or servicing the meter.
- Do not touch live terminals.
- Verify correct wiring connections to prevent damage to the meter or electrical system.
- The meter must be installed in a dry, well-ventilated area, free from excessive dust, corrosive gases, and direct sunlight.
3. Vokatra mihoatraview
The Acrel DTSD1352 is a compact and robust three-phase multi-function energy meter. It features a clear LCD display for real-time data, intuitive control buttons, and various connection terminals.

Sary 3.1: anoloana view of the DTSD1352 meter. This image displays the main LCD screen showing power readings (e.g., 0.00 kW), the "SET" button, and three orange arrow buttons for navigation. Terminal blocks are visible at the top and bottom for electrical connections.

Sary 3.2: zorony view of the DTSD1352 meter. This perspective highlights the compact design and the various input/output terminals on the top and bottom, as well as the side labeling for model identification.
4. Famaritana
The following table outlines the key technical specifications of the Acrel DTSD1352 energy meter. For detailed information, refer to the product datasheet.

Sary 4.1: Detailed technical specifications. This image presents a table covering various parameters such as reference voltage (3*57.7/100V, 3*220/380V, 3*380V), reference frequency (50Hz), maximum current (6A, 80A), accuracy (Class 0.5S), communication interface (RS485, MODBUS-RTU), dimensions (127*88*70 mm), and environmental conditions (operating temperature -25~55℃, humidity ≤95%).
| fikirana | sarobidy |
|---|---|
| Reference Voltage | 3*57.7/100V, 3*220/380V, 3*380V |
| Frequency reference | 50Hz |
| Maximum Current | 6A, 80A (depending on model) |
| Accuracy of active kWh | Kilasy 0.5S |
| Fifandraisana Interface | RS485 |
| Fifandraisana Protocol | MODBUS-RTU |
| refy (L*W*H) | 127mm * 88mm * 70mm |
| Temperature miasa | -25 ℃ hatramin'ny 55 ℃ |
| Temperature fitehirizana | -40 ℃ hatramin'ny 70 ℃ |
| Hamandoana | ≤95% (Tsy misy condensation) |
| Altitude | <2000m |
| Lanja entana | 7.1 ounces (eo ho eo amin'ny 200g) |
5. Fametrahana sy Wiring
Proper installation and wiring are critical for the accurate and safe operation of the DTSD1352 meter. Refer to the diagrams below for connection methods.

Sary 5.1: Wiring diagrams. This image illustrates two primary wiring methods: a 3-phase 4-wire (3P4W) direct connection where power lines (A, B, C, N) connect directly to the meter, and a connection via Current Transformers (CTs) for higher current applications, showing the CTs connected to the respective phase lines and then to the meter.
5.1 Direct Connection (3P4W)
For direct connection, ensure the phase lines (A, B, C) and neutral (N) are connected to the corresponding terminals on the meter. This method is typically used for lower current applications where the meter can directly handle the load current.
- Connect Phase A to terminal 'A'.
- Connect Phase B to terminal 'B'.
- Connect Phase C to terminal 'C'.
- Connect Neutral to terminal 'N'.
- Ataovy azo antoka fa voaaro tsara ny fifandraisana rehetra.
5.2 Connection via Current Transformers (CTs)
For higher current applications, the DTSD1352 meter can be connected via external Current Transformers (CTs). This method scales down the current to a measurable level for the meter.
- Install the CTs on each phase line (A, B, C).
- Connect the secondary windings of the CTs to the corresponding current input terminals (e.g., Ia*, Ia, Ib*, Ib, Ic*, Ic) on the meter.
- Ensure the polarity of the CTs is correct (P1/K to the source side, P2/L to the load side, and S1/S2 to the meter). Incorrect polarity will result in inaccurate readings.
- Ampifandraiso ny voltage inputs (Ua, Ub, Uc, N) directly from the respective phases and neutral to the meter.
- It is recommended to install a fuse on the voltage input lines for protection.
Important: Always ensure the CT secondary circuit is closed before applying power to the primary circuit. Never open the secondary circuit of a live CT.
6. Fampandehanana
Once installed and powered, the DTSD1352 meter will automatically begin measuring. The LCD display shows various parameters, which can be navigated using the control buttons.
6.1 Fitetezana Aseho
- LCD Display: Mampiseho fandrefesana amin'ny fotoana tena izy toy ny voltage, current, active power, reactive power, power factor, frequency, and total energy (kWh).
- "SET" Button: Used to enter the parameter setting mode or confirm selections.
- Arrow Buttons (Left, Right, Up, Down): Used to navigate through different display screens or adjust parameter values in setting mode.
6.2 Reading Energy Data
Press the arrow buttons to cycle through the various measurement screens. Common readings include:
- Angovo mavitrika manontolo (kWh)
- Forward Active Energy (kWh)
- Reverse Active Energy (kWh)
- BOKYtage (V) per phase
- Current (A) per phase
- Active Power (kW) per phase and total
- Reactive Power (kVar) per phase and total
- Hery Factor (PF)
- Frequency (Hz)
6.3 RS485 Fifandraisana
The meter supports RS485 communication with MODBUS-RTU protocol. This allows for remote reading of meter data and configuration. Refer to the MODBUS communication protocol document for detailed register addresses and commands.
7. Fikojakojana
The DTSD1352 energy meter is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.
- Fanadiovana: Keep the meter clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
- Fifandraisana: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to inaccurate readings or overheating.
- Tontolo iainana: Ataovy azo antoka fa mijanona ao anatin'ny mari-pana sy hamandoana voafaritra ny tontolo iasana.
- calibration: The meter is factory calibrated. If you suspect inaccuracies, contact qualified service personnel for recalibration.
8. Famahana olana
This section provides solutions to common issues you might encounter with the DTSD1352 meter.
| OLANA | Antony mety hitranga | vahaolana |
|---|---|---|
| Meter display is blank. | No power supply to the meter. | Check the main power supply and wiring connections to the meter's voltage input terminals. Ensure fuses are intact. |
| Inaccurate energy readings. | Incorrect wiring, incorrect CT ratio setting (if applicable), faulty CTs, or meter malfunction. | Verify all wiring connections according to Section 5. Ensure CT polarity is correct. Check if the CT ratio programmed in the meter matches the physical CTs. If issues persist, contact technical support. |
| Ny tsy fahombiazan'ny fifandraisana RS485. | Incorrect wiring of RS485 terminals (A/B), incorrect communication parameters (baud rate, parity, address), or software issue. | Check RS485 A and B terminal connections. Verify communication settings (baud rate, data bits, stop bits, parity, meter address) in your master device match the meter's settings. Ensure proper termination resistors are used if necessary. |
| Meter shows "Error" or specific error codes. | Internal fault or specific operational issue. | Note down the error code and consult the full product manual or contact technical support for specific error code interpretations and solutions. |
9. Warranty sy fanohanana
This product is manufactured by TGLGTQPX and sold under the Acrel brand. For specific warranty terms and conditions, please refer to the documentation provided at the time of purchase or contact your vendor. General support for the Acrel DTSD1352 meter can be obtained through the manufacturer's official channels or your authorized distributor.
For technical assistance, troubleshooting beyond this manual, or spare parts, please contact:
- Mpanamboatra: TGLGTQPX
- Marika vokatra: Acrel
- Modely: DTSD1352
- (Contact information such as website or email would typically be provided here by the manufacturer.)