1. Fampidirana

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station. This device is designed to initiate a fire alarm signal when manually activated, contributing to the overall safety and security of a building's occupants.

The Simplex 4099-9006 is an IDNet addressable manual pull station with an integrated LED indicator, ensuring reliable communication within compatible fire alarm systems.

2. Information momba ny fiarovana

WARNING: Installation and servicing of this device must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).

  • Always disconnect power to the fire alarm control panel before installing or servicing the pull station.
  • Hamarino tsara ny fiorenana mba hisorohana ny fahatafintohinana elektrika.
  • Do not paint over the pull station or obstruct its operation.
  • Test the pull station regularly as part of a comprehensive fire alarm system testing schedule.
  • This device is not intended for outdoor use unless specifically rated for such environments.

3. Vokatra mihoatraview

The Simplex 4099-9006 is a robust, red-colored manual fire alarm pull station featuring a double-action mechanism (push then pull). It includes an integrated LED indicator for status feedback.

Simplex 4099-9006 Double Action Fire Alarm Pull Station with installation instructions

Figure 3.1: Simplex 4099-9006 Double Action Fire Alarm Pull Station. This image displays the front of the red pull station with "FIRE ALARM" and "PUSH PULL DOWN" labels, alongside a detailed instruction sheet for installation and mounting, and a small bag of mounting hardware.

Ny singa fototra dia ahitana:

  • Activation Handle: The "PUSH PULL DOWN" mechanism used to initiate an alarm.
  • LED famantarana: Provides visual status of the device (e.g., normal, alarm, trouble).
  • sakana terminal: For connecting to the fire alarm control panel's IDNet circuit.
  • Mounting Plate/Housing: Secures the device to a standard electrical box or surface.

4. Fametrahana & Fametrahana

The Simplex 4099-9006 pull station can be installed using either single-gang or two-part mounting methods, typically on a standard 4-inch square electrical box (not supplied).

4.1 Fanamarinana mialoha ny fametrahana

  • Verify that the fire alarm control panel is powered off.
  • Ensure the mounting location is clean, dry, and meets local code requirements for height and accessibility.
  • Confirm all necessary tools and hardware are available (e.g., screwdriver, wire strippers, mounting screws).

4.2 Fomba fametrahana

Refer to the installation diagrams provided with the product and shown in Figure 3.1 for visual guidance.

4.2.1 Single-Gang Mounting

  1. Secure the pull station directly to a standard single-gang electrical box.
  2. Ensure the device is flush with the wall surface.

4.2.2 Two-Part Mounting

  1. Install the backbox or mounting plate first, typically a 4-inch square electrical box.
  2. Mount the pull station assembly onto the installed backbox.
  3. This method may be used for flush trim or surface mounting applications.

4.3 Tariby

The 4099-9006 is an IDNet addressable device. Connect the pull station to the IDNet circuit of the fire alarm control panel using appropriate gauge wiring, following the wiring diagram provided on the device or in its specific installation sheet. Ensure polarity is correct.

  • Connect the incoming and outgoing IDNet circuit wires to the designated terminals.
  • Ataovy azo antoka fa azo antoka ny fifandraisana rehetra ary tsy misy short.

4.4 Aorian'ny fametrahana

  • Once installed and wired, restore power to the fire alarm control panel.
  • Verify the LED indicator on the pull station shows a normal operating status (typically a slow flash).
  • Perform a functional test of the pull station as described in the "Operating Instructions" section.

5. Torolàlana miasa

The Simplex 4099-9006 features a double-action activation mechanism to prevent accidental alarms.

5.1 Activating the Alarm

  1. ATOSEHO: Firmly push the "PUSH" bar located at the top of the activation handle.
  2. PULL DOWN: Once the "PUSH" bar is depressed, pull the handle "PULL DOWN" until it latches in the alarm position.
  3. Upon activation, the pull station will send an alarm signal to the fire alarm control panel, and the integrated LED will illuminate steadily (or change to a rapid flash, depending on system programming) to indicate an alarm state.

5.2 Resetting the Pull Station

To reset the pull station after an alarm, a special key (not included with this specific model, as indicated by "No Key" in the product title, implying a different reset mechanism or system-level reset) or tool is typically required to return the handle to its normal, non-alarm position. For the 4099-9006, the reset mechanism is internal and does not require a key. Simply push the handle back into its original position. The fire alarm control panel must also be reset to clear the alarm condition from the system.

6. Fikojakojana

Regular maintenance ensures the reliable operation of your Simplex 4099-9006 pull station. All maintenance should be performed by qualified personnel.

6.1 Fanamarinana mahazatra

  • Visual Inspection (Monthly): Check for any physical damage, obstructions, or signs of tampering. Ensure the pull station is clean and clearly visible.
  • LED Status (Monthly): Verify the LED indicator is showing a normal operating status (e.g., slow flash).

6.2 Functional Testing (Annually or as per local codes)

Functional testing should be conducted by a certified fire alarm technician.

  1. Notify building occupants and the monitoring station before testing.
  2. Activate the pull station as described in "Operating Instructions".
  3. Verify that the fire alarm control panel receives the alarm signal and initiates appropriate responses (e.g., sounding alarms, notifying monitoring station).
  4. Reset the pull station and the fire alarm control panel.
  5. Confirm the pull station returns to a normal operating state.

6.3 Fanadiovana

Clean the exterior of the pull station with a soft, damp lamba. Aza mampiasa mpanadio na solvents mikikisana, satria mety hanimba ny endrika ivelany na ny singa anatiny izany.

7. Famahana olana

This section addresses common issues you might encounter with the Simplex 4099-9006 pull station. For complex issues, contact a qualified fire alarm technician.

OLANAAntony mety hitrangavahaolana
Pull Station does not activate alarm.Incorrect activation procedure; wiring issue; device fault; control panel issue.Ensure proper push-then-pull action. Check wiring connections. Verify control panel status. Contact technician if problem persists.
LED indicator is off or shows trouble.No power; wiring fault; device fault; control panel trouble.Check power to the control panel. Inspect wiring for breaks or shorts. Consult control panel manual for trouble codes. Contact technician.
Fanairana diso.Accidental activation; faulty device; wiring issue.Reset the pull station and control panel. Inspect for physical damage or obstructions. If recurring, contact technician.
Pull station handle does not reset.Olana anatiny momba ny mekanisma; poti-javatra.Ensure no debris is obstructing the mechanism. Gently attempt to push the handle back. If it remains stuck, the unit may need replacement.

8. Famaritana

endri-javatraantsipirihany
Laharana modelyS4099-9006
Karazana vokatraDouble Action Manual Fire Alarm Pull Station
Marikasimplex,
mpanamboatraSIMPLEX Grinnell
lokoMENA
Fomba fampahavitrihanaPush then Pull Down
Key Requirement for ResetNo Key Required (Internal Reset)
fifandraisanaIDNet Addressable
Endri-javatra mitambatraLED famantarana
Lanja entana0.5 kilao (eo ho eo amin'ny 8 oz)
Ny refin'ny vokatra6 x 6 x 4 santimetatra (eo ho eo)
UPC643485653004
Daty misy voalohany21 Desambra 2015
Simplex 4099-9006 product packaging boxSimplex 4099-9006 product packaging box with PID and Part No.

Figure 8.1: Product packaging for the Simplex 4099-9006, showing the brown cardboard box with product identification labels. The labels confirm PID 4099-9006 and Part No. 06501211.

9. Warranty & Fanohanana

9.1 Fampahalalana momba ny fiantohana

This Simplex product is typically covered by a manufacturer's warranty against defects in materials and workmanship. Specific warranty terms and duration may vary. Please refer to the original purchase documentation or contact Simplex customer service for detailed warranty information.

Note: The product listing mentions "12 months warranty" and "30 days return if not satisfied". This information is from a third-party seller and may not reflect the official manufacturer's warranty. Always verify with the manufacturer.

9.2 Fanohanana ara-teknika

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact a certified fire alarm technician or the manufacturer directly.

Simplex Customer Support: Please visit the official SimplexGrinnell website or refer to your product packaging for contact details.

For general inquiries, you may also refer to the Simplex brand page on Amazon.

Documents mifandraika - S4099-9006

Preview Simplex IDNet/MAPNET II Tobim-piantsonan'ny fanairana afo azo ampiasaina - Data momba ny vokatra
Fampahalalana amin'ny antsipiriany momba ny tobin'ny fanairana afo amin'ny alàlan'ny Simplex 4099 Series, mifanaraka amin'ny rafitra IDNet sy MAPNET II. Ny endri-javatra, ny famaritana, ny safidy fametrahana ary ny fifantenana ny vokatra ho an'ny modely isan-karazany, ao anatin'izany ny hetsika tokana, hetsika roa (breakglass sy push), ary safidy NO GRIP. Mifanaraka amin'ny fepetra takian'ny ADA ary voatanisa ao amin'ny UL, ULC, FM ary CSFM.
Preview Simplex Addressable Manual Stations: IDNet/MAPNET II Peripherals
Explore Simplex addressable manual fire alarm stations, detailing their features, single/double action types, NO GRIP options, and compatibility with IDNet/MAPNET II systems. Includes mounting and specification information.
Preview Simplex 2099 Series Single and Double Action Manual Fire Alarm Stations Datasheet
Datasheet for Simplex 2099 Series non-coded, non-addressable manual fire alarm pull stations. Covers features, operation types, application references, product selection, mounting options, and specifications.
Preview Simplex 4010ES: Systèmes de commande d'extinction automatique pour gicleurs
Guide technique Simplex 4010ES détaillant les modules de commande pour les systèmes d'extinction automatique par gicleurs, couvrant les modes déluge et préventif, avec spécifications, homologations et schémas de câblage.
Preview Simplex 4099-9801C IDNet™ 2-Stage Station IAM Installation Instructions
Installation instructions for the Simplex 4099-9801C IDNet™ 2-Stage Station Individual Addressable Module (IAM). Covers mechanical installation, electrical connections, and address configuration for fire alarm systems.
Preview Simplex 4004 Fire Alarm Control Panel: Installation and Operation Instructions
Comprehensive guide for installing, operating, and programming the Simplex 4004 Fire Alarm Control Panel (FACP), including system overview, requirements, wiring, module descriptions, and troubleshooting.